Surveillance of various facilities has to be possible at any time for maintenance personnel. To allow for an easy optical and acoustical display of actual states or events on-site, universal and robust annunciator systems are required.
The comprehensive portfolio of EES monitoring products enables solutions that fit seamlessly into your structures.
EES – annunciator systems serve a multitude of application ranges. With research and development, production and sales all under one roof at our headquarters in Germany, we are able to respond quickly to customer needs and to stay at the cutting edge of technology.
Aside from that our products benefi t from more than 40 years of experience in countless applications worldwide. They are used in Substations|Transformer stations| Facility monitoring | Site monitoring | Industrial facilities | Pumping stations | and many more…
EES offers a comprehensive portfolio, which includes annunciators for almost any task and size of site. The range of products stretches from simple indication devices up to networkable annunciator systems with
communication interface, e.g. according to standards IEC 61850 or IEC 60870-5-101/104. Of course all EES – annunciators focus on high functionality together with ease-of-use.
Standard fault annunciators
For simple indication or monitoring tasks the EES portfolio offers different standard fault annunciators for panel mounting to visualize operation or alarm conditions. Depending on the type first-up or new-value processing, NO or NC triggering, as well as the assignment to collective reports can be configured. The general alarm processing is otherwise fixed.| TYPE | LAB | SSM | BSM-C |
|---|---|---|---|
![]() | ![]() | ![]() |
|
| Signal inputs | 8/16 | 8/16 | 8/16/24/32/40/48 |
| LED-Colours | green/red/yellow/white | green/red | red and green |
| exchangeable | ✓ | - | parameterisable |
| Signal processing | |||
| pre-set | - (LAB -M) | ✓ | ✓ |
| parameterisable | DIP-Switch (LAB-M) | DIP-Switch ( SSM-A) | DIP-Switch |
| Relay output | |||
| Collective report | ✓ (1 x LAB-M) | ✓ up to 2 | ✓ (3) |
| Horn internal / Relay | - | - /✓ | ✓/ ✓ |
| Live-Contact | - | Live LED | ✓ |
| 1:1 Relays internal | - | - | ✓ (opt.) |
| 1:1 Relais external | - | ✓ ( opt. SSM-R) | ✓ (opt.) |
| Buttons | |||
| Lamp test | - | ✓ | ✓ |
| Acknowledgement Lamp | - | ✓ | ✓ |
| Acknowledgement Horn | - | ✓ | ✓ |
| Functional test | - | - | ✓ |
| Status retention on power failure | - | - | ✓ |
| Read more | Read more | Read more |
Fault annunciators with extended functionality
Fault annunciators with enhanced functionality are predestined for the solution of complex reqiurements not only by the expandable design. In a cluster comprising of several cascaded fault annunciators larger plants or fields can be monitored. In opposite to the standard fault annunciators comprehensive manupilations of each channel can be carried out.| TYPE | FSM | BSM-P | WAP-P |
|---|---|---|---|
![]() | ![]() | ![]() |
|
| Signal inputs | 10 | 8/16/24/32/40/48 | 24 |
| Display | Dropflaps + LED | angular LED | Windows any size |
| LED-Colours | green | red and green | 16 different |
| exchangeable | - | parameterisable | parameterisable |
| Signal processing | |||
| pre-set | ✓ | ✓ | ✓ |
| parameterisable | DIP-Switch / Software | DIP-Switch / Software | DIP-Switch / Software |
| Relay output | |||
| Collective report | ✓ (2) | ✓ (3) | ✓ (3) |
| Horn internal / Relay | ✓/✓ | ✓/✓ | ✓/✓ |
| Live-Contact | ✓ | ✓ | ✓ |
| 1:1 Relays internal | - | ✓ (opt.) | ✓ (opt.) |
| 1:1 Relais external | - | ✓ (opt.) | ✓ (opt.) |
| Buttons | |||
| Lamp test | ✓ | ✓ | ✓ |
| Acknowledgement Lamp | ✓ | ✓ | ✓ |
| Acknowledgement Horn | ✓ | ✓ | ✓ |
| Functional test | ✓ | ✓ | ✓ |
| Status retention on power failure | + Display | ✓ | ✓ |
| Read more | Read more | Read more |
Fault annunciating systems with protocol interface
Fault annunciating devices with standardized protocol provide on the one hand the serial or networkable acquiring of plant conditions and the corresponding display of the resprective signal input, as well as the forwarding of parallel to in- or output messages to superior systems. From SCADA Systems even single or double commands can be carried out via relays triggered by protocol telegrams. The systems of this group present as an I/O device the ideal form of a "ragman".| TYPE | LAB-SER | USM | WAP-K |
|---|---|---|---|
![]() | ![]() | ![]() |
|
| Signal inputs | 16 | 8/16/24/32/40/48 | 24 |
| Display | round LED | angular LED | Windows any size |
| LED-Colours | red | red and green | 16 different |
| Parameterisable | - | ✓ | ✓ |
| Signal processing | |||
| pre-set | ✓ | ✓ | ✓ |
| Parameterisable | via Modbus | Software | Software |
| Relay output | |||
| Collective report | - | ✓ (3) | ✓ (3) |
| Horn internal / Relay | - | ✓/✓ | ✓/✓ |
| Live-Contact | only LED | ✓ | ✓ |
| 1:1 Relays internal | - | ✓ (opt.) | ✓ (opt.) |
| 1:1 Relais external | - | ✓ (opt.) | ✓ (opt.) |
| Buttons | |||
| Lamp test | - | ✓ | ✓ |
| Acknowledgement Lamp | - | ✓ | ✓ |
| Acknowledgement Horn | ✓ | ✓ | ✓ |
| Functional test | - | ✓ | ✓ |
| Status retention on power failure | - | ✓ | ✓ |
| Protocol | |||
| CS31 | ✓ | - | - |
| Modbus RTU | ✓ | - | - |
| IEC 60870-5-101/-104 | - | ✓ | ✓ |
| IEC 61850 | - | ✓ | ✓ |
| Read more | Read more |